FS-8700-21 LonWorks Manual Page 63 of 72
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com
Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: [email protected]
SNVT_pumpset_mn
Data Length
8
Suggested Data Array Formats
Byte, Uint16, Float
Data Item 1
pset_main_pump
Measurement
Units
Values Range
Invalid Value
motor_state_t
N/A
0 .. 7
255 (0xFF)(MOTOR_NUL)
Data Item 2
pset_booster_pump
Measurement
Units
Values Range
Invalid Value
motor_state_t
N/A
0 .. 7
255 (0xFF)(MOTOR_NUL)
Data Item 3
pset_prio_level
Measurement
Units
Values Range
Invalid Value
priority_level_t
N/A
0 .. 11
255 (0xFF)(PR_NUL)
Data Item 4
pset_process_ready
Measurement
Units
Values Range
Invalid Value
Boolean_t
Bit
0, 1
255 (0xFF)(BOOL_NUL)
Data Item 5
pset_emerg_stop
Measurement
Units
Values Range
Invalid Value
Boolean_t
Bit
0, 1
255 (0xFF)(BOOL_NUL)
Data Item 6
pset_main_pumpd_ena
Measurement
Units
Values Range
Invalid Value
Boolean_t
Bit
0, 1
255 (0xFF)(BOOL_NUL)
Data Item 7
pset_boost_pumpd_ena
Measurement
Units
Values Range
Invalid Value
Boolean_t
Bit
0, 1
255 (0xFF)(BOOL_NUL)
Data Item 8
pset_maint_req
Measurement
Units
Values Range
Invalid Value
Boolean_t
Bit
0, 1
255 (0xFF)(BOOL_NUL)