Appendix B.2. Checking LONWORKS® Network Using Echelon’s NodeUtility.exe
Run Nodeutil.exe.
Press Service Pin on all LONWORKS® Devices.
Press ‘F’ to find Nodes.
Press ‘L’ to List Nodes, Confirm that all Nodes can be seen.
Press ‘G’ (Goto) each Node and:
o Dump Node Domain Table ( ‘D’, Enter ).
o Confirm Domain ID is correct ( usually , “F” ).
o Record Node.
o Confirm that Subnet is “1”.
o Confirm that Size is “1”.
Press ‘L’ (List) Network Variables.
o Record SNVT Type and Index.
Appendix B.3. Neuron Systems
Newron Systems may produce the following Error message “bindings lost after power-cycle” The solution to this is
to place the FieldServer in the Configured state which will cause the bindings to be committed to the Neuron and
they will remain after a power cycle.
Procedure:
1) Make the bindings in NL220
2) Place devices in ONLINE mode or state.
3) Refer to the following Screencap for assistance in placing the FieldServer in the Configured state.