FS-8700-21 LonWorks Manual Page 46 of 72
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com
Tel
: (408) 262 2299 Fa
x
: (408) 262 2269 Toll Free
: (888) 509 1970 emai
l
: [email protected] -2, 147, 483, 647... 2, 147, 483, 647
-3.40282E38... 3.40282E38
Values Range – These are the only values that will be allowed for the SNVT, e.g. a value of 101 will not be
processed in a read or write on SNVT_Switch’s Value data item.
Invalid Value – The Invalid value is used to force the data item’s value should a value outside the value range be
encountered in a read or write. Should the invalid value be N/A ( Not Applicable ), the data item’s value will be
bounded by the indicated values range, e.g. an incoming read value of 101 will be stored as 100 for SNVT_Switch’s
Value data item. Note that in some cases both the type and raw values are specified. Raw values are not of the
same type of the SNVT’s measurement type, i.e. they are not scaled.
Data Item – SNVT’s containing more than one data item have a name specified for each item. This name can be
used in the SNVT_Option field of a Map Descriptor to isolate only this one item.
Suggested Data Array Formats
Raw: 65,535 (0xFFFF)
Type: 655.35
Suggested Data Array Formats
Suggested Data Array Formats
Alm_Location00,
..Alm_Location05
index of NV causing
alarm
Alm_Value00,
..Alm_Value03