FS-8700-21 LonWorks Manual Page 39 of 72
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com
Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: [email protected]
Now go onnet in Care and commission your controllers.
If this will be installed on a SymmetrE frontend you will need to create an XIF file for LNS to use to commission
the device on synchronization. Use the Ruinet software or NodeUtil182 (available for free download at
www.echelon.com). Ensure that the XIF is not created until everything has been configured and
commissioned properly.
Appendix B.6. Circon_SI
Circon_SI does not recognize whitespace; %; -
The maximum number of Network Variables under Circon_SI is limited to 255 per node.
Set the Connection_Type parameter in the configuration file per the following example. This will ensure that all
illegal characters are replaced with underscores, and that the number of Network Variables per Node is limited to
255 in the configuration.
Example
// Client Side Connections
Connections
Adapter
, Protocol
, Connection_Type
LonWorks
, LonWorks
, Circon_SI