5.3.14 Map Descriptor Example 10 - Binary Value (Zone and Area Machine)
A read from the Binary Value Data Array which is shared by a BACNet IP Map Descriptor will return the current value of a system variable in the Lutron eLumen panel. The
value returned is inactive (0) if the system variable is zero and active (1) if non-zero. The Lutron Machine Map Descriptor regularly polls the Lutron panel to retrieve the
system variable values. A write to the Binary Value Data Array will set the system variable to 255 on active (1) write or to zero on inactive (0) write.
BACNet IP Map Descriptor
// Client Side Map Descriptors
Map_Descriptors
Map_Descriptor_Name
, Data_Array_Name
, Data_Array_Offset
, Function
, Node_Name
, Data_Type
, Object_ID
, Length
, Relinquish_Default
SMD00_BV
, Binary_Value
, 0
, Passive
, Virtual_BCU_11
, BV
, 1
, 512
, 0
Lutron Machine Map Descriptor
// Client Side Map Descriptors
Map_Descriptors
Map_Descriptor_Name
, Data_Array_Name
, Data_Array_Offset
, Function
, Node_Name
, Grafik_Command
, Sys_Var
, Length
Zone_var_0
, Binary_Value
, 0
, Arco
, LUT_GRF6_0
, Sys_Var_Val_Bin
, 0
, 512