FS-8700-97 Lutron Machine Manual Page 13 of 24
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com
Tel
: (408) 262 2299 Fax
: (408) 262 2269 Toll Free
: (888) 509 1970 emai
l
: [email protected]m 5.3.7 Map Descriptor Example 4 - Analog Output 1 (Area Machine)
A write to the Analog Output Data Array which is shared by a BACNet IP Map Descriptor will command an area to a preset scene on the Lutron eLumen panel. Scenes
range from 0 to 65535 and area numbers range from 0 to 511
BACNet IP Map Descriptor
// Client Side Map Descriptors
Lutron Machine Map Descriptor
// Client Side Map Descriptors
The area field must be used to indicate the start area number that will be associated with the first element of the Data Array specified under Data_Array_Name. Area
numbers increase with the Length field in association with increasing offset into the Data Array.