FS-8700-16 BACnet PTP Serial Driver Manual Page 10 of 32
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll Free: (888) 509-1970 email: support@fieldserver.com
4.5 Client Side Map Descriptors
Name of this Map Descriptor. This is used for
Object_Name Property. Refer to Appendix A.1.
Up to 32 alphanumeric characters
Name of Data Array where data is to be stored
in the FieldServer
One of the Data Array names from
“Data_Array” section
Starting location in Data Array
0 to (“Data_Array_Length” -1)
Function of Client Map Descriptor
4.5.1 Driver Related Map Descriptor Parameters
Name of Node to fetch data from
One of the node names
specified in “Client Node
Descriptor”
Object_Type
(Alias = Data_Type)
Type of object. Refer to Appendix D.1 for more
information.
AI, AO, AV, BI, BO, BV, MI,
MO, MV, NC
Object_Instance
(Alias = Address)
Instance of the object on the device.
The BACnet property to be read.
Scaling zero in Data Array
Scaling max in Data Array
Scaling zero in Connected Node
Scaling max in Connected Node
Used to create an array of sequential Object_Instances
on an Object_Type.
1 to max point count of
the FieldServer, 1
When referencing Multistate properties, allows the user
to specify the index of the property to be read. If 1 is
specified, the first one will be read, if 2 is specified, the
second will be read, etc. If 0 is specified, the driver will
return the total number (count) of array items linked to
the property. If the parameter is not specified, a list of
all items will be returned. Refer to Appendix A.3
0 to max number of array
items in the BACnet
Property, -
4.5.2 Timing Parameters
Rate at which data is polled