Fieldserver FS-8700-03 DF1 Manual do Utilizador Página 8

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 16
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 7
FS-8700-03 DF1 Driver Manual Page 8 of 16
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com
Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: [email protected]
5.3 Client Side Map Descriptor Parameters
5.3.1 FieldServer Related Map Descriptor Parameters
Column Title
Function
Legal Values
Map_Descriptor_Name
Name of this Map Descriptor
Up to 32 alphanumeric characters
Data_Array_Name
Name of Data Array where data is to be
stored in the FieldServer
One of the Data Array names from
Section 4.
Data_Array_Offset
Starting location in Data Array
0 to (Data_Array_Length-1) as specified
in Section 4.
Function
Function of Client Map Descriptor
Rdbc, Wrbc, Wrbx
5.3.2 Driver Related Map Descriptor Parameters
Column Title
Function
Legal Values
Node_Name
Name of Node to fetch data from
One of the Node names specified in Section 5.2
File_Type
File type in PLC
N, F, B, I, O
5
File_Number
File Number in PLC
0-255
Address
Starting address of read block
0 255
Length
Length of read block
1-255
Scan_Interval
Rate at which data is polled
0-32000s, 1.0s
Data_Array_Low_Scale*
Scaling zero in Data Array
-32767 to 32767, 0
Data_Array_High_Scale*
Scaling max in Data Array
-32767 to 32767, 100
Node_Low_Scale*
Scaling zero in Connected Node
-32767 to 32767, 0
Node_High_Scale*
Scaling max in Connected Node
-32767 to 32767, 100
5
Not all PLC’s can support all File_Types. Refer to DFS for further information.