Fieldserver Envirotronics SystemsPlus FS-8700-88 Manual do Utilizador Página 18

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 49
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 17
FS-8700-88 Envirotronics SystemsPlus Page 18 of 49
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldServer.com
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: supp[email protected]m
4.4.29. Map Descriptor Example 26 - set audible alarm = Boolean
// Client Side Map Descriptors
Map Descriptor
Map_Descriptor_Name, Data_Array_Name, Data_Array_Offset, Function, Node_Name, SysPlus_Data_Type, Length
Audible_Alarm, Audible_Alarm_0, 0, wrbx, SYSPLUS_01, Audible_Alarm, 1
A Boolean value of 1 for “on” or 0 for “off” must be written to Data_Array_Name at Data_Array_Offset to trigger this command.
4.4.30. Map descriptor Example 27 - read software version
// Cleint Side Map Descriptors
Map Descriptor
Map_Descriptor_Name, Scan_Interval, Data_Array_Name, Data_Array_Offset, Function, Node_Name, SysPlus_Data_Type, Length
Sw_Version, 0s, Sw_Version, 0, rdbc, SYSPLUS_01, Sw_Version, 1
4.4.31. Map Descriptor Example 28 - read events
// Client Side Map Descriptors
Map Descriptor
Map_Descriptor_Name, Scan_Interval, Data_Array_Name, Data_Array_Offset, Function, Node_Name, SysPlus_Data_Type, Length
All_Event_States, 0s, All_Event_States, 0, rdbc, SYSPLUS_01, All_Events, 10
The retrieved event states will be stored as follows in Data_Array_Name:
( A value of 1 will be stored for “on” or 0 for “off )
Offset from Data_Array_Offset Description
0 Event_0 state
1 Event_1 state
2 Event_2 state
.. ..
9 Event_9 state
Vista de página 17
1 2 ... 13 14 15 16 17 18 19 20 21 22 23 ... 48 49

Comentários a estes Manuais