FS-8700-01 Modbus RTU/ASCIIFS-8700-01_Modbus_RTU.doc Driver Manual Page 13 of 21
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com
Tel
: (408) 262 2299 Fa
x
: (408) 262 2269 Toll Free
: (888) 509 1970 email
: suppo[email protected] 6.3 Server Side Map Descriptor Parameters
6.3.1 FieldServer Specific Map Descriptor Parameters
Name of this Map Descriptor
Up to 32 alphanumeric characters
Name of Data Array where data is to be
stored in the FieldServer
One of the Data Array names from
Section 4
Starting location in Data Array
0 to (Data_Array_Length -1) as specified
in Section 4
Function of Server Map Descriptor
6.3.2 Driver Specific Map Descriptor Parameters
The name of the Node
being represented.
One of the Node names specified in Section 6.2
Coil, Discrete_Input, Input_Register, Holding_Register,
Single_Coil, Single_Register, Slave_ID
FC01, FC02, FC03, FC04,
FC05, FC06, FC15, FC16
Address_Type = Modicon_5digit
- (Dash), Single_Register, Single_Coil
Starting address of read
block
Address_Type = Modicon_5digit
Scaling zero in Data Array
Any signed 32 bit integer in the range:
-2,147,483,648 to 2,147,483,647. 0
Scaling max in Data Array
Any signed 32 bit integer in the range:
-2,147,483,648 to 2,147,483,647. 100
Scaling zero in Connected
Node
Any signed 32 bit integer in the range:
-2,147,483,648 to 2,147,483,647. 0
Scaling max in Connected
Node
Any signed 32 bit integer in the range:
-2,147,483,648 to 2,147,483,647. 100
Optional only for Modicon_5digit addressing, and only if Single writes do not need to be forced